专业提供CE认证,建材CE认证,地板CE认证,玻璃棉CE认证,石材CE认证,钢纤维CE认证,门窗CE认证,瓷砖CE认证,防水板CE认证,保温材料CE认证等!
用户登录
  • 用户名:
  • 密 码:
业务领域
增值服务
合作机构
联系我们
地址:中国江苏省南京市江东中路118号德盈大厦16F
电话:(+86) 025-8658 3475
传真:(+86) 025-8658 3475
邮箱:info@hksmartps.com
网址:www.hksmartps.com
EN1366-2防火挡板耐火试验Fire damper (EI 120 S)
发布日期:2024-6-18 11:28:30   阅读次数:157
EN 1366-2 防火挡板耐火试验
EN 1366-2 Fire resistance tests for service installations-Part 2: Fire dampers.
EN 1366-2 服务设施的耐火试验-第2部分:防火阀。

EN 1366-2规定了一种确定防火阀耐火性的方法,该防火阀安装在设计用于承受高温下的热量和烟雾和气体通过的防火隔离元件中。本标准与EN 1363-1一起使用。

该方法主要用于机械设备的测试。它不适合在未经修改的情况下测试吊顶中的防火阀。

EN1366-2防火挡板耐火试验Fire damper
EI 60 (ve ho i & o ) S
EI 120 (ve ho i & o ) S
E: Integrity (against flames & hot gases)
I: Insulation (against heat)
S: Smoke leakage (against gases & smoke)
ve: Vertical installation
ho: Horizontal installation
i & o: Fire direction, outside & inside duct
60 Minutes integrity and insulation
120 Minutes integrity

防火阀fire damper
安装在通风、空气调节系统的送、回风管道上,平时呈开启状态,火灾时当管道内烟气温度达到70°C时关闭,并在一定时间内能满足漏烟量和耐火完整性要求,起隔烟阻火作用的阀门。
防火阀一般由阀体、叶片、执行机构和温感器等部件组成。

排烟防火阀 fire damper in smoke-venting system
安装在机械排烟系统的管道上,平时呈开启状态,火灾时当排烟管道内烟气温度达到280°C时关闭,并在一定时间内能满足漏烟量和耐火完整性要求,起隔烟阻火作用的阀门。
排烟防火阀一般由阀体、叶片、执行机构和温感器等部件组成。

排烟阀smoke damper
安装在机械排烟系统各支管端部(烟气吸入口)处,平时呈关闭状态并满足漏烟量要求,火灾或需要排烟时手动和电动打开,起排烟作用的阀门。带有装饰品或进行过装饰处理的阀门称为排烟口。
排烟防火阀一般由阀体、叶片、执行机构等部件组成。

EN15650防火挡板欧盟CE认证_CE Marking for Fire dampers 
请参考 http://www.cprce.com/Certification/CEforConstruction/1563.html

防火挡板欧盟CE认证标准-EN 15650:2010
Fire dampers are CE-marked according EN 15650:2010 and tested according to EN 1366-2 and EN 13501-3 standard. Fire dampers are used as safety-related components in ventilation systems to prevent fire and smoke spreading through ducting.

EN 15650:2010 Ventilation for buildings - Fire dampers 
EN 15650:2010 建筑通风,防火挡板

This European Standard applies to fire dampers that are to be used in conjunction with fire separating elements to maintain fire compartments. This standard specifies requirements and gives reference to the test methods defined for fire dampers, which are intended to be installed in Heating, Ventilating and Air Conditioning (HVAC) installations in buildings. All fire dampers close automatically in response to raised temperatures indicating fire. Details are given for the provision of evaluation of conformity and marking of fire dampers.
EN 15650适用于与防火分隔元件一起使用以维持防火分区的防火阀。EN 15650规定了安装在建筑物供暖、通风和空调(HVAC)装置中的防火阀的要求,并参考了其测试方法。所有防火阀都会自动关闭,以响应指示火灾的升高温度。提供了防火阀一致性评估和标记的详细信息。

南京睿督为欧盟公告号Notified Body实验室授权合作实验室,可以直接受理EN15650防火挡板欧盟CE认证。

南京睿督公司咨询电话:025-8658 3475    400-603-6575
网址:www.hksmartps.com     www.cprce.com
邮箱:info@hksmartps.com  
微信:firetesting  或 17714189018